Request a Quote

Ratings & specifications

Voltage Transformer Selection

Choose voltage transformers around the system voltage, required secondary circuits, connected burden, and intended use. Confirm protection, insulation, accuracy, and physical configuration with the project engineer.

01 / BUILT WITH PURPOSE SWITCHGEAR BUILDERS OHIO

Installed switchboard lineup beneath overhead conduit
REPRESENTATIVE
EQUIPMENT
01
Made in USAAmerican manufacturing
02
UL 891 assembliesFor applicable low-voltage switchboards
03
Short lead timesTiming quoted per project

Start With System Voltage and Application

Voltage transformer selection begins with the circuit being measured and the purpose of the measurement. Establish nominal and maximum system voltage, frequency, grounding method, and whether the installation is single-phase or three-phase. Confirm whether the device will serve metering, protective relaying, synchronization, indication, or more than one function.

The equipment context matters: a transformer installed in low-voltage switchgear has different insulation and construction requirements from one applied to medium-voltage equipment. Specify the switchgear type, bus arrangement, and connection point. The responsible engineer should verify compatibility with the one-line diagram, system study, utility requirements, and applicable codes.

Determine the Required Ratio

The primary-to-secondary ratio translates system voltage into a usable instrument voltage. Define the primary connection and the required secondary value from the meter, relay, or control-device inputs. For three-phase circuits, identify whether the transformer connections must provide phase-to-neutral, phase-to-phase, or both measurements.

Do not select a ratio from nominal voltage alone. Check expected operating range, grounding and fault conditions, connected device limits, and the measurement scheme. Where a grounded-wye primary or broken-delta secondary is contemplated, document the intended function and diagram. The engineer must confirm ratio and winding connections before fabrication.

Match Accuracy and Burden to the Load

Burden is the load imposed on a transformer secondary by instruments, relays, wiring, and associated devices. List each connected device and estimate its burden at the required operating conditions. Include lead length and conductor size, since circuit resistance can affect voltage delivered to remote equipment and measurement accuracy.

Accuracy requirements depend on use. Revenue or operational metering may have different needs from indication or protective relaying, and the applicable accuracy class must be specified rather than assumed. Check the transformer's capability across the expected burden range and confirm that multiple circuits will not exceed its stated limits.

Plan Primary-Side Protection

Primary protection must be coordinated with the system and the transformer's construction. Identify whether the design calls for fuses, another approved protective arrangement, or a specific switchgear configuration. Confirm available fault current, voltage class, interrupting requirements, and the intended isolation method with the responsible engineer.

Protection details are not interchangeable across equipment types. Fuse selection and mounting depend on the application, manufacturer design, and governing electrical requirements; do not infer a fuse rating from the transformer ratio. Provide the one-line diagram and protection criteria so the equipment configuration can be reviewed against the installation and coordination study.

Design Secondary Circuits and Grounding

Define each secondary winding's destination, nominal voltage, circuit identification, and terminal arrangement. Explain whether separate circuits are required for metering and protection, or whether a shared circuit is permitted by the design. Identify test switches, shorting or isolation provisions, terminal blocks, and cable entry preferences when they affect the assembly.

Secondary grounding and overcurrent protection require deliberate coordination. State the grounding point and intended protection arrangement, and show how circuits leave the switchgear. Multiple grounds, open secondary connections, or unprotected wiring can undermine measurement or create unsafe conditions. Have the engineer review the schematic, applicable code requirements, and relay instructions.

Separate Monitoring From Protection Needs

Monitoring applications commonly support voltage indication, energy measurement, power quality instruments, or supervisory systems. Confirm required phase values, accuracy, output compatibility, and whether the secondary feeds devices with distinct burdens. Communications equipment may rely on a meter's data output, but it does not remove the need to define the transformer inputs correctly.

Protection applications may use voltage signals for undervoltage, overvoltage, directional, synchronism-check, or ground-fault functions. Identify relay models or input specifications, operating logic, and required winding connections. Confirm behavior during abnormal conditions and switching transitions with the protection engineer; the selected transformer should follow the relay scheme, not a generic application assumption.

Confirm Insulation and Physical Integration

Specify the equipment voltage class, insulation requirements, and environmental conditions at the installation. For medium-voltage applications, provide system grounding information and the relevant design requirements; UL 891 applies to low-voltage switchboards, not medium- or high-voltage equipment. Low-voltage switchgear and switchboards also require configuration-specific review.

Physical details influence fit and serviceability. Share compartment location, bus or conductor connection, available space, access direction, mounting constraints, and cable routing. Identify temperature, altitude, indoor or outdoor exposure, and any unusual contamination or vibration concerns. Final dimensions, clearances, and construction details should be confirmed for the actual assembly.

Prepare Complete Information for a Quote

A useful quote package includes the one-line diagram, system voltage and frequency, grounding method, transformer ratio, winding connections, accuracy needs, burden estimate, and intended monitoring or protection functions. Add primary protection expectations, secondary schematics, equipment type, applicable specifications, and requested documentation so the proposed configuration can be assessed accurately.

Also provide quantity, project schedule, installation environment, interface requirements, and any preferred metering or relay devices. U.S.-built equipment using American components can be custom fabricated, with short lead times and nationwide shipping; confirm schedule and scope for the specific build. The responsible engineer, utility, and AHJ should review applicable design requirements.

PROJECT PARAMETERS

Details make
the difference.

Every project is different. Use these points as a starting place for a conversation about your requirements.

Discuss your specifications
SPECIFICATION OVERVIEW01 — 06
Project specification overview
Equipment & scopeDefined by project requirements
Voltage classConfirm for the application
Current ratingConfirm for the application
Applicable standardsUL 891 for applicable low-voltage switchboards; other standards per specification
ManufacturingMade in USA with American components
Lead timeQuoted per project

Final configuration, ratings, standards, and timing are confirmed with your quote.

LET'S GET TO WORK

Tell us what
you’re building.

Share the essentials and start a conversation about equipment for your project.

Prefer to talk?(951) 403-5738

Email our team at saleselectricalbuyers@gmail.com.

SWITCHGEAR BUILDERS OHIO
BUILT FOR THE WORK AHEAD

PROJECT INQUIRY

Request a quote

This form opens your email application where supported. Review and send your request to saleselectricalbuyers@gmail.com from your email app; nothing is submitted directly through this website.

* Required fields