Start with the Process and Load List
Oil and gas facilities can combine continuous process loads with large, intermittently started motors. Pumps, compressors, fans, heaters, and auxiliary systems may operate under different duty cycles and criticality levels. Begin with a load list that identifies voltage, phase, full-load current, starting method, operating profile, and whether each load is essential.
Also identify planned expansion, standby generation, and loads that must transfer or shed during an outage. These details affect bus capacity, feeder space, protective-device selection, and coordination with upstream sources. A quote is more useful when it includes one-line diagrams, load schedules, and the project’s basis of design rather than a headline ampere rating alone.
Choose Equipment by Voltage and Function
At low voltage, a UL 891 switchboard may suit distribution duties when the design and project specifications call for that construction. UL 1558 low-voltage switchgear is a distinct equipment category that may be selected where the application requires its construction and functional characteristics. Neither designation should be treated as interchangeable without engineering review.
Medium-voltage distribution is a separate design scope, with equipment selected for the system voltage, available fault current, switching needs, and applicable standards. UL 891 does not cover medium- or high-voltage equipment. Confirm the service and distribution arrangement, including utility ownership boundaries, before establishing the equipment lineup and requesting a proposal.
Coordinate Motor Control with Starting Demands
Motor control can be arranged in motor control centers, switchgear, or separate assemblies, depending on voltage, motor size, process layout, and maintenance strategy. Determine which motors need across-the-line starters, reduced-voltage starting, or variable-frequency drives. Starting current and acceleration time can affect voltage dip, feeder sizing, protection, and generator or transformer selection.
For each controlled motor, provide horsepower or kilowatt rating, voltage, nameplate data when available, driven-load information, starts per hour, and control philosophy. Identify local and remote operation, interlocks, alarms, and any required communications. Drive location and cooling arrangements should be checked against ambient conditions and enclosure requirements rather than assumed from a standard configuration.
Assess Site Conditions and Hazardous Areas
Oil and gas sites vary from climate-controlled process buildings to outdoor installations exposed to heat, cold, moisture, dust, salt, or vibration. Share the installation location, ambient temperature range, elevation, contamination concerns, and enclosure location. These conditions can influence ventilation, space planning, material choices, and equipment arrangement.
Hazardous-area classification is a project-specific engineering determination, not a blanket attribute of all equipment used in the industry. Provide the classified-area documentation, including class, division or zone, and group where applicable, along with the proposed equipment location. The responsible engineer and AHJ should confirm required boundaries, wiring methods, and equipment suitability.
Develop Protection and Control Requirements
Protective devices must be coordinated with the source, conductors, connected loads, and system operating modes. Supply available fault-current data, transformer information, grounding method, and upstream settings when known. Study results may shape interrupting ratings, trip functions, selective coordination, arc-flash analysis, and choices for tie breakers or multiple incoming sources.
Define how operators and the control system will monitor and control the lineup. Relevant points may include breaker status, metering, alarms, trip indication, and communications protocols. Specify functional needs and interfaces without assuming every feature is standard. Have the responsible engineer verify protection, control, and interlocking against the project documents and applicable codes.
Plan for Continuity, Maintenance, and Expansion
Production priorities help determine whether a facility needs separate buses, tie capability, redundant sources, or a defined load-shedding sequence. These arrangements involve tradeoffs in cost, complexity, operating procedures, and fault exposure. Document normal and emergency operating modes, including how generators, utility feeds, and process loads are expected to interact.
Maintenance access and future work deserve attention before the lineup is fixed. Confirm room dimensions, door and aisle clearances, cable entry direction, conduit zones, lifting access, and environmental constraints. Identify spare feeder provisions or planned additions by type and size. These are design inputs to evaluate, not features that can be presumed for every assembly.
Prepare a Quote Package That Supports Design
A practical RFQ package includes the one-line diagram, equipment schedules, specifications, site conditions, and requested standards or certifications. Include system voltage, continuous current, fault-current data, incoming and outgoing connections, enclosure location, and control requirements. Mark open items clearly so the proposed scope can distinguish confirmed requirements from assumptions needing review.
For motor control, attach the motor list and identify starter or drive preferences, bypass needs, control voltage, communications, and process interlocks. Provide delivery destination, installation schedule, and any drawing-submittal requirements. Our team builds new equipment in the U.S. with American components and can custom-fabricate configurations; project details determine feasibility and lead time.
Coordinate Engineering, Delivery, and Installation
Before release, reconcile the equipment drawings with utility requirements, protection studies, cable plans, room layout, and the latest project specification. Confirm any required inspections, documentation, and interface responsibilities with the utility and AHJ. The responsible engineer should review final ratings, protection settings, grounding, and installation details for the actual site conditions.
Equipment selection is only one part of a successful project; receiving access, rigging, field connections, commissioning scope, and operator needs also affect execution. Share schedule milestones and shipping constraints early. We supply new switchgear and power distribution equipment to Ohio and nationwide, with custom fabrication and short lead times discussed against each project’s scope.