Request a Quote

Switchgear knowledge center

What Is Selective Coordination?

Selective coordination aims to have the protective device nearest an overcurrent condition operate first, limiting interruption to the affected circuit where required and practicable. Achieving it depends on system design, device characteristics, and verified coordination studies.

01 / BUILT WITH PURPOSE SWITCHGEAR BUILDERS OHIO

Motor control center lineup inside an industrial building
REPRESENTATIVE
EQUIPMENT
01
Made in USAAmerican manufacturing
02
UL 891 assembliesFor applicable low-voltage switchboards
03
Short lead timesTiming quoted per project

The Purpose of Selective Coordination

Selective coordination is the arrangement of overcurrent protective devices so that, for specified fault-current conditions, the device closest to the affected circuit opens before upstream devices. The objective is to disconnect the faulted branch while keeping other loads energized when the system and applicable requirements permit that outcome.

The term does not promise that every fault will interrupt only one breaker or fuse. Device behavior depends on fault magnitude, duration, equipment characteristics, and the available short-circuit current. Engineers evaluate the actual protective-device combinations and operating ranges rather than relying on product labels or a general assumption.

Where Requirements and Project Goals Apply

Whether selective coordination is required depends on the installation, adopted codes, system function, and project specifications. Certain essential or emergency functions may have specific coordination provisions, while other distribution systems may pursue coordination as an operational objective. The responsible electrical engineer should identify the applicable rules for each system.

Requirements can apply across multiple levels, from a branch-circuit device through feeders and service equipment. The design team should define the relevant paths and loads, including alternate sources where present. The authority having jurisdiction interprets and enforces adopted requirements; confirm design assumptions with the AHJ and utility as applicable.

Trace the Full Protective-Device Path

A useful coordination review starts at the load and traces every upstream protective device toward the source. That path may include a branch breaker, panelboard or switchboard feeder device, distribution switchgear, and service protection. A single coordinated pair does not establish coordination across other devices in the same system.

Document each device’s type, frame or fuse class, trip or rating settings, and location, along with conductor and transformer information that affects fault current. Include tie breakers, generator sources, and transfer equipment when they can change the current path. Missing or incorrect data can invalidate the study’s conclusions.

How Engineers Evaluate Device Coordination

Engineers commonly compare time-current characteristics for protective devices, considering both normal clearing behavior and the range of available fault currents. A coordination study may use manufacturer data and engineering software to assess whether downstream protection operates before upstream protection for the conditions under review.

Curves alone are not always enough to resolve close or overlapping behavior, particularly in the instantaneous region or with current-limiting devices. The engineer may need additional manufacturer-specific information and assumptions about tolerances. Coordination findings should be interpreted alongside short-circuit, equipment-duty, and arc-flash analyses rather than in isolation.

System Conditions That Can Change Results

Available fault current varies with source strength, transformer impedance, conductor length and size, and the operating configuration. A system with utility and generator sources, parallel transformers, or closed ties can have different fault levels and current paths in different modes. Coordination needs to be checked for the configurations required by the project.

Settings that improve selectivity in one range can affect other design constraints. For example, delayed clearing may increase equipment exposure or affect arc-flash results, while a low instantaneous setting may interrupt upstream protection during a downstream fault. The engineer must balance coordination with equipment ratings, protection objectives, and applicable safety requirements.

Switchgear and Switchboard Configuration

New distribution equipment can be configured with protective devices selected for the project’s electrical design, but coordination is not established by enclosure choice alone. The specified lineup, device types, ratings, accessories, and available adjustment ranges must match the study assumptions. Verify that proposed settings can be implemented and documented in the delivered equipment.

UL 891 switchboards are distinct from UL 1558 low-voltage switchgear, and both are distinct from medium-voltage equipment. These standards describe different equipment categories; none by itself guarantees selective coordination. Confirm the system voltage, service and feeder arrangement, construction requirements, and applicable product standard with the engineer and project specifications.

Information to Provide for a New Equipment Quote

For a useful quote, provide one-line diagrams, system voltage and phase, source and transformer data, available fault-current information, and the intended normal and emergency configurations. Include load or feeder schedules, required equipment category, upstream and downstream protective-device details, and any coordination study or written performance criteria available.

Identify the project location, applicable specifications, required submittals, enclosure conditions, and desired delivery schedule. State which devices are new equipment to be supplied and which existing upstream devices must be included in coordination assumptions; this does not change the scope into used-equipment procurement. Unresolved design inputs should be clearly listed for engineering review.

Review, Documentation, and Design Responsibility

Before release, compare proposed device selections and settings against the approved study and project documents. Changes to a breaker, fuse, trip unit, transformer, conductor, or system configuration can alter results, so substitutions should receive engineering review. Record final settings and coordination assumptions for commissioning and future maintenance personnel.

A U.S. manufacturer building new equipment with American components can provide custom fabrication and nationwide shipping, with lead times confirmed for the specific scope. The responsible engineer should verify coordination and protection design; coordinate utility data and AHJ requirements where relevant. A quote can address documented requirements, but cannot replace project-specific engineering approval.

PROJECT PARAMETERS

Details make
the difference.

Every project is different. Use these points as a starting place for a conversation about your requirements.

Discuss your specifications
SPECIFICATION OVERVIEW01 — 06
Project specification overview
Equipment & scopeDefined by project requirements
Voltage classConfirm for the application
Current ratingConfirm for the application
Applicable standardsUL 891 for applicable low-voltage switchboards; other standards per specification
ManufacturingMade in USA with American components
Lead timeQuoted per project

Final configuration, ratings, standards, and timing are confirmed with your quote.

LET'S GET TO WORK

Tell us what
you’re building.

Share the essentials and start a conversation about equipment for your project.

Prefer to talk?(951) 403-5738

Email our team at saleselectricalbuyers@gmail.com.

SWITCHGEAR BUILDERS OHIO
BUILT FOR THE WORK AHEAD

PROJECT INQUIRY

Request a quote

This form opens your email application where supported. Review and send your request to saleselectricalbuyers@gmail.com from your email app; nothing is submitted directly through this website.

* Required fields